HVI power Conductor
Details

Can be used up to an equivalent separation distance s ≤ 90 cm (in air) or s ≤ 180 cm (solid material).
Thus, the following maximum conductor lengths can be realised with one down conductor depending on the class of lightning protection system (LPS):
LPS I max. 11.25 m
LPS II max. 15.0 m
LPS III/IV max. 22.50 m
Lightning current carrying capability of 200 kA (10/350 µs) tested according to EN 62561-1.
The HVI power long Conductor meets the requirements of EN 62561-2.
A processing temperature of -5 to +40 °C and a permanent temperature range (at fixed installation) of -30 up to +70 °C must be observed.