Reinforcement technology
Fixed earthing points and connecting clamps for equipotential bonding. Earth electrode seals and wall bushings for safe insertion into the building. Rebar clips for lightning-current-carrying connection of the reinforcement to the earthing system.
Fixed Earthing Terminals
For installation in concrete as a corrosion-free connection to the earth-termination system for protective equipotential bonding and / or functional equipotential bonding of the down conductor, e.g. to the reinforcement of buildings.
Please observe the following minimum screw lengths for the M10 and M12 double threads:
35 mm of M10 (thread length 40 mm)
15 mm of M12 (thread length 20 mm)
Please observe the following minimum screw lengths for the M10 and M12 double threads:
35 mm of M10 (thread length 40 mm)
15 mm of M12 (thread length 20 mm)
Fixed Earthing Terminals with flexible Connection Clamp
For installation in concrete as a flexible corrosion-free connection to the earth-termination system for protective equipotential bonding and/or functional equipotential bonding of the down conductor, e.g. to the reinforcement of buildings.
Fixed Earthing Terminal M16
With M16 connection thread for higher current loads (50 Hz), e.g. for connecting the ring equipotential bonding system with the earth-termination systems of power installations with nominal AC voltages over 1 kV (transformer earthing).
Wall Bushings
With MV clamp made of StSt (V4A) for round conductors 8–10 mm.
Water-pressure-tight wall bushing for leading earthing conductors / equipotential bonding conductors through brickwork or walls; with M10 threaded rod made of StSt.
For subsequent installation through borehole (Ø14 mm) or through spacer in the formwork.
Test for water pressure-tightness up to 1 bar features an installation depth of 10 m in stagnant water.
Water-pressure-tight wall bushing for leading earthing conductors / equipotential bonding conductors through brickwork or walls; with M10 threaded rod made of StSt.
For subsequent installation through borehole (Ø14 mm) or through spacer in the formwork.
Test for water pressure-tightness up to 1 bar features an installation depth of 10 m in stagnant water.
Water-Pressure-Tight Wall Bushings for White Tank
For installation in the formwork.
Is suitable for water-pressure-tight wall bushings; e.g. for connecting the ring earth electrode with the equipotential bonding bar or the equipotential bonding conductor in the foundation.
Is suitable for water-pressure-tight wall bushings; e.g. for connecting the ring earth electrode with the equipotential bonding bar or the equipotential bonding conductor in the foundation.
Sealing Collar for round and flat Conductors
Water-pressure-tight sealing collar for round conductors (Ø8-10 mm) and flat conductors (30 x 3.5 mm) with waterproof foundation slabs / walls (e.g. watertight concrete constructions).
With torque control spanner for easy tightening of the two stainless steel tensioning straps.
MPA-tested to 5.0 bar, methane-resistant, radon-safe (as per FHRK leaflet MB 101)
Waterproof concrete construction guideline: Load class 1 + 2
With torque control spanner for easy tightening of the two stainless steel tensioning straps.
MPA-tested to 5.0 bar, methane-resistant, radon-safe (as per FHRK leaflet MB 101)
Waterproof concrete construction guideline: Load class 1 + 2
Connecting Clamps for Fixed Earthing Terminals and Reinforcement
For connecting the reinforcement with clamping piece.
For round conductors or fixed earthing terminals with simultaneous fixing in the formwork.
Arrangement:
(II) = parallel
(+) = cross
For round conductors or fixed earthing terminals with simultaneous fixing in the formwork.
Arrangement:
(II) = parallel
(+) = cross
End Pieces
Screwed to the fixed earthing terminal to connect, e.g. an equipotential bonding bar or structural parts such as steel girders, etc.
Connection Clamps with Threaded Bolt
For connecting round and flat conductors to fixed earthing terminals with M10 / M12 thread (e.g. Part Nos. 478 011, 478 200) and M16 thread (Part No. 478 027).
Clamps with M10 thread are also suitable for installation on the rear side of the fixed earthing terminal (without connecting shaft), e.g. to connect a flat strip.
Clamps with M10 thread are also suitable for installation on the rear side of the fixed earthing terminal (without connecting shaft), e.g. to connect a flat strip.
Threaded Adapter
For connection to fixed earthing terminals with M10 thread, lock nut and spring washer, for use in case of perimeter insulation or thermal insulation composite systems.
DEHNclip Rebar Clamp
In accordance with DIN 18014 ""Earthing systems for buildings – Planning, execution and documentation"", the equipotential bonding conductor / foundation earth electrode must be connected to the reinforcement of the foundation slab every 2 metres.
For connecting reinforcing steel mesh or reinforcements with round and flat conductors.
Arrangement: (II) = parallel (+) = cross
Quick and safe:
The DEHNclip rebar clip for quick connection of the earth electrode to the reinforcement without tools. DEHNclip is tested for a lightning current carrying capability of 50 kA (10/350 μs) in accordance with DIN EN 62561-1.
For connecting reinforcing steel mesh or reinforcements with round and flat conductors.
Arrangement: (II) = parallel (+) = cross
Quick and safe:
The DEHNclip rebar clip for quick connection of the earth electrode to the reinforcement without tools. DEHNclip is tested for a lightning current carrying capability of 50 kA (10/350 μs) in accordance with DIN EN 62561-1.
Connecting Clamps for Foundation Earth Electrodes
For connecting round and flat conductors in the concrete foundation.
For T, cross and parallel connections, without having to insert the conductor.
Arrangement:
(II) = parallel
(+) = cross
For T, cross and parallel connections, without having to insert the conductor.
Arrangement:
(II) = parallel
(+) = cross
Connecting Clamps for Foundation Earth Electrodes and Reinforcements
For connecting round and flat conductors in the concrete foundation or reinforcing steel meshes and reinforcements with round and flat conductors.
Arrangement:
(II) = parallel
(+) = cross
Arrangement:
(II) = parallel
(+) = cross
Connecting Clamps for Reinforcements
In accordance with DIN 18014 ""Earthing systems for buildings – Planning, execution and documentation"", the equipotential bonding conductor / foundation earth electrode must be connected to the reinforcement of the foundation slab every 2 metres.
For connecting reinforcing steel mesh or reinforcements with round and flat conductors.
Arrangement: (II) = parallel (+) = cross
For connecting reinforcing steel mesh or reinforcements with round and flat conductors.
Arrangement: (II) = parallel (+) = cross